Step 2: Determine Voltage Drop – According to CMAA, the voltage drop to the unit motors shall not be more than 3% from the power taps to the load at the farthest point on the conductor run.  To determine the voltage drop use the appropriate formula in the following table.

 

 

*See Conductor Engineering Data Table below for

values of Z and R.

 

Maximum voltage drops that are 3% of various

Supply voltages are:

 

 

*** For additional calculation clarification and information on Voltage Drop: Click Here